With the Luna EN.SURE cable strain measurement system it is possible to measure the strain put on your power cable when unforeseen events happen and take the appropriate action - saving time and money on downtime and making sure your cables are always ready to run at maximum capacity and preventing large-scale cable faults. Let LIOS EN.SURE ensure a reliable supply of electrical power for today’s world.
Long power cables and other similar structures are susceptible to forces from many unforeseen influences – excavators digging a new road, an anchor being pulled behind a boat, earthquakes, etc. By integrating a Luna EN.SURE next to your cables you now have the possibility to monitor your cables and assess damages that may be forced upon them.
The EN.SURE is a series of controllers for distributed structure monitoring (DSM) that is based on proprietary Brillouin measurement technology. Its major advantages are the excellent distance range and measurement performance in combination with the passively cooled and maintenance-free industrial design. It exhibits a superior strain and temperature resolution and accuracy in comparison to other technologies. The excellent performance is achieved in both, single- and double-ended fiber configurations.
Features
- Highly reliable industrial design
- Signal processing based on patented Raman OFDR Technology
- Superior hotspot detection along the whole sensor cable length
- Maintenance-free and simplified outdoor installation capability
- International Approvals and Certificates – type tested and accredited
Contact us now
Distance ranges of DSM Models
EN.SURE DSM -050, -100, -200, -300, -400, -500 |
5 km, 10 km, 20 km, 30 km, 40 km, 50 km |
Optical data
Optical Channels (internal) |
1, 2, 3, 4, 6, 8, 9, 12 or 16 |
Fiber Configuration |
No loop or termination required |
Optical Connector (s) |
E2000 / APC |
Fiber types |
Single-mode 9/125, e.g. ITU-T G.652, G.655 or G.657 |
Laser Classification |
Class 1M (IEC60825-1) eye-safe wavelenght |
Measurement Performance*
Sampling Interval |
0.25, 0.5 or 1 m |
Spatial Resolution |
1, 2, 3 or 5 m |
Temperature Resolution @ 10 dB Optical Loss |
<1°C |
Strain Resolution, minimum |
<2 µε |
Strain Resolution @ 10dB Optical Loss |
<20 µε |
Temperature Accuracy |
2°C |
Measurement Time |
1 to 20 min |
*Measurement performance parameters are interdependent
Data Storage/Communication/Interfaces
Internal SSD Storage |
8, 16, 32 or 64 GB |
Communication Interfaces |
2x Ethernet TCP/IP, USB, (optional: WLAN, GSM) |
Communication Protocols (options) |
XML, MODBUS, DNP3, IEC60870, IEC 61850 |
Programable Inputs/Outputs |
4/10 |
Fixed Outputs |
Collective fault and alarm |
I/O Board (optional)* |
4 inputs/12 outputs |
Analogue Sensors Interface Board (optional)* |
4x Pt100, 2x 0(4)-20 mA and 2x 0-10 V |
Analogue Outputs (optional external module) |
4 - 20 mA |
*2 optional boards can be installed
Mechanical Data
Rack Space |
19-inch rack, 3 height units |
Dimensions HxWxD |
13.3 x 43.9 x 40.3 |
Weight |
15 kg |
Environmental Conditions
Power Consumption, max. (DC/AC options) |
40 W / 45 W |
Operating Voltage (DC-1 option) |
12 ... 24 V DC (-15%/+10%) |
Operating Voltage (DC-2 option) |
24 ... 48 V DC (-15%/+10%) |
Mains Voltage (AC option) |
100 ... 240 V Ac 50 ... 60 Hz / 110 ... 220 V DC (-15%/+10%) |
Conformity to Standards
Electrical Safety |
IEC/UL 61010-1, LV directive 2014/35/EC, CAN/CSA-C22.2 |
EMC* |
EN61326-1, EN61000-62,3 -4-2, 3, 5, 5, 6, 8, 11, -3-2, 3, FCC 47 CFR Ch. 1 part 15 |
Hazardous Substances, waste |
RoHS directive 2011/657EC, WEE directive 2002/96/EC |
Environmental Testing* |
IEC 60068-2-6, 14, 27, 30 |
Environmental Safety (IEC 61508)* |
Hardware design compliant to Safety Integrity Level SIL2 |
Explosion Safety (option)* |
EX II (1) [Ex op is T4 GA] IIC/II 81) [Ex op is Da] IIIC/I (m1) [Ex op is MA] |